| PIPE SIZE (in.) | Weight (lbs) | w/Water (lbs) | SPAN (ft) | ROD |
|---|---|---|---|---|
| 3/8″ | 0.6 | 0.7 | 7 | 3/8″-16 |
| 1/2″ | 0.8 | 0.9 | 7 | 3/8″-16 |
| 3/4″ | 1.1 | 1.3 | 7 | 3/8″-16 |
| 1″ | 1.7 | 2.1 | 7 | 3/8″-16 |
| 11/4″ | 2.3 | 2.9 | 7 | 3/8″-16 |
| 11/2″ | 2.7 | 3.6 | 9 | 3/8″-16 |
| 2″ | 3.6 | 5 | 10 | 3/8″-16 |
| 21/2″ | 5.8 | 7.9 | 11 | 1/2″-13 |
| 3″ | 7.6 | 10.8 | 12 | 1/2″-13 |
| 31/2″ | 9.1 | 13.4 | 13 | 1/2″-13 |
| 4″ | 10.8 | 16.3 | 14 | 5/8″-11 |
| 5″ | 14.6 | 23.2 | 16 | 5/8″-11 |
| 6″ | 19 | 31.5 | 17 | 3/4″-10 |
| 8″ | 28.5 | 50.1 | 19 | 3/4″-10 |
| 10″ | 40.5 | 74.6 | 22 | 7/8″-9 |
| 12″ | 51.1 | 102.1 | 23 | 7/8″-9 |
| 14″ | 63 | 121.5 | 25 | 1″-8 |
| 16″ | 83 | 159.5 | 27 | 1″-8 |
| 18″ | 105 | 202.2 | 28 | 1″-8 |
| 20″ | 123 | 243.4 | 30 | 11/4″-7 |
| 24″ | 171 | 345.2 | 32 | 11/4″-7 |
- Based on Mss Table 3 & 4
- Based on ASTM A53-86
- * Many codes require pipe hangers to be spaced every 10 ft. regardless of size. Check local codes.
- 1 Cubic Ft. of water weighs 62.41 lbs.
- 1 gallon (U.S.) weighs 8.335 lbs.
- Spacing and capacities are based on water filled pipe. Closer hanger spacing may be required where additional valves and fittings increase the load.