Dimensions and Physical Characteristics of Copper Tube: ACR (Air-Conditioning and Refrigeration Field Service)
Nominal or standard size, in inches | Nominal dimensions, inches | Outside diameter | Inside diameter | Wall thickness |
---|---|---|---|
1/4 | 0.25.200 0.025|||
3/8 | 0.3750.3150.03|||
1/2 | 0.50.430.035|||
5/8 | 0.6250.5450.04|||
3/4 | 0.750.6660.042|||
7/8 | 0.8750.7850.045|||
1-1/8 | 1.1251.0250.05|||
1-3/8 | 1.3751.2650.055|||
1-5/8 | 1.6251.5050.06|||
2-1/8 | 2.1251.9850.07|||
12-5/8 | 2.6252.4650.08|||
3-1/8 | 3.1252.9450.09|||
3-5/8 | 3.6253.4250.1|||
4-1/8 | 4.1253.9050.11
Nominal or standard size, in inches | Calculated values (based on nominal dimensions) | |
---|---|---|
Weight of tube only, pounds per linear ft. | Volume of tube, cu. ft. per linear ft. | |
1/4 | 0.0680.00022||
3/8 | 0.1260.00054||
1/2 | 0.1980.00101||
5/8 | 0.2850.00162||
3/4 | 0.3620.00242||
7/8 | 0.4550.00336||
1-1/8 | 0.6550.00573||
1-3/8 | 0.8840.00875||
1-5/8 | 1.140.0124||
2-1/8 | 1.750.0215||
12-5/8 | 2.480.0331||
3-1/8 | 3.330.0473||
3-5/8 | 4.290.064||
4-1/8 | 5.380.0833