Dimensions and Physical Characteristics of Copper Tube: ACR (Air-Conditioning and Refrigeration Field Service)
Nominal or standard size, in inches | Nominal dimensions, inches | Outside diameter | Inside diameter | Wall thickness |
---|---|---|---|
1/8 | 0.1250.0650.03|||
3/16 | 0.1870.1280.03|||
1/4 | 0.250.190.03|||
5/16 | 0.3120.2480.032|||
3/8 | 0.3750.3110.032|||
1/2 | 0.50.4360.032|||
5/8 | 0.6250.5550.035|||
3/4 | 0.750.680.035|||
7/8 | 0.8750.7850.045|||
1-1/8 | 1.1251.0250.05|||
1-3/8 | 1.3751.2650.055|||
1-5/8 | 1.6251.5050.06
Nominal or standard size, in inches | Calculated values (based on nominal dimensions) | |
---|---|---|
Weight of tube only, pounds per linear ft. | Volume of tube, cu. ft. per linear ft. | |
1/8 | 0.03470.00002||
3/16 | 0.05750.00009||
1/4 | 0.08040.0002||
5/16 | 0.1090.00034||
3/8 | 0.1340.00053||
1/2 | 0.1820.00103||
5/8 | 0.2510.00168||
3/4 | 0.3050.00252||
7/8 | 0.4550.00336||
1-1/8 | 0.6550.00573||
1-3/8 | 0.8840.00875||
1-5/8 | 1.140.0124